Shuttle® Ultrasonic Level Transmitter
The shuttle is a complete ultrasonic non contact level sensor with a two pump controller included in the controller, the sensor is uniquely designed with a narrow 3° beam angle allowing measurement in the narrowest of applications.
The sensor is IP68 and can withstand flooding without damage to the sensor, the graphical display makes commissioning easy including well mapping functions to eliminate false echos.
Shuttle® Sensors
200570/71 Sensor
Range: 15 m (fluids) 6 m (solids)
Frequency: 30 kHz
Spread: 3°
Deadband: 35 cm
Temperature: – 20° to + 60° C
Materials: PP, POM. Mounting: ISO
Cable: Shielded, oil resistant PVC insulation, length 12 m/50 m
Enclosure: IP 68, watertight, withstands max. 1 bar submersion
CE-approvals: EN 50081-1, EN 50082-1
200640/41/42 Sensor
Range: 12 m (fluids), 5 m (solids)
Frequency: 40 kHz
Spread: 7°
Deadband: 35 cm
Temperature: – 20° to + 60° C
Materials: PTB+PC, glass reinforced epoxy. Mounting: NPT
Cable: Shielded, oil resistant PVC insulation, length 12m. (Max. 100 m. extension with 690010
cable.)
Enclosure: IP 68, watertight, withstands max. 1 bar submersion
CE-approvals: EN 50081-1, EN 50082-1
200630/31/32 Sensor
Range: 25 m (fluids), 10 m (solids)
Frequency: 30 kHz
Spread: 6°
Deadband: 80 cm
Temperature: – 20° to + 60° C
Materials: PTB+PC, glass reinforced epoxy. Mounting: NPT
Cable: Shielded, oil resistant PVC insulation, length 12 m. (Max. 100 m. extension with 690010
cable.)
Enclosure: IP 68, watertight, withstands max. 1 bar submersion
CE-approvals: EN 50081-1, EN 50082-1
200660 Sensor
Range: 10 m (fluids), 5 m (solids)
Frequency: 50 kHz
Spread: 6°
Deadband: 35 cm.
Temperature: – 20° to + 60° C
Materials: PP, PVDF. Mounting: ISO
Cable: Shielded, oil resistant PVC insulation, length 12 m. (Max. 100 m. extension with 690010
cable.)
Enclosure: IP 68, watertight, withstands max. 1 bar submersion
CE-approvals: EN 50081-1, EN 50082-1
- Multiple sensors with measuring ranges from 10 cm to 25 m.
- Learns how the tank is arranged with piping, pumps and other items interfering with the measurement.
- Ignores turbulence and electrical interference (even a slow moving mixer can pass through without influencing the measurement).
- Two output relays for level/system alarm or alternating pump control with duty and standby cycles.
- 4-20 mA output with zero and span adjustment.
- Indicates strength of echo signal with a bar graph.
- Narrow ultrasonic pulse signal concentrates signal strength for minimum sensitivity to foam/sludge on the liquid surface.
- Easy to read LCD-display for both setup and indication.
- Actual level indicated with bar graph and digits in millimeters, centimeters, meters, feet and inches.
- Readout can be chosen as relative or absolute level.
- 10-30 V DC or 230 V AC supply.
- FM approved sensors for hazardous areas.
Range: 0-12 m., 0-15 m., 0-25 m. (depending on sensor)
Span: (4/20 mA) From 0-10 cm to 0-12 m/15 m/25 m
Supply voltage: 230/115 V AC ± 10 % or 10-30 V DC
Power consumption: Approx. 2 W
Temperature range: – 20° to + 60° C
Input: From ultrasonic sensor
Measurement accuracy: Better than ± 0.2 %
Outputs: Analog: 4 – 20 mA, max. load 500 Ω, Digital: 2 x relays with programmable NO/NC function, Max. 1 A resistive load @ 50 V
Indication: LCD display with four digits and symbols
Operation: Function keypad behind front panel
Enclosure: IP 67
Test approvals: CE: EN 50081-1, EN 50082-1, UL: File E194021